三相电压不对称时谐波与基波有功、无功电流的精确检测方法研究
Research on precision detection method of harmonics, fundamental active current and reactive current in the case of unsymmetrical three-phase voltage

作  者: ; ; ; ;

机构地区: 华南理工大学电子与信息学院

出  处: 《继电器》 2003年第4期6-9,20,共5页

摘  要: 当三相电压不对称时ip-iq 检测法会产生误差 ,本文对ip-iq 检测法在三相电压不对称时存在的误差进行了分析。之后提出了一种改进的ip-iq 检测法 ,在该检测法中用基于低通滤波的A相正序电压提取单元代替原ip-iq 检测法中的锁相环 ,以提取A相正序电压。仿真与试验证明在三相电压畸变且不对称时该检测方法仍然能正确地检测出谐波与基波有功。 The i p i q detecting method will cause errors when three phase voltage is imbalance. The errors are analyzed in this paper. A improved i p i q detecting method is put forward. In order to select phase A fundamental positive sequence voltage, a voltage selected unit based on low pass filter is used to replace the phase lock loop of i p i q detecting method. Simulation and experiment show that the improved i p i q detecting method can accurately detect harmonics, active current and reactive current of fundamental when three phase voltage is imbalance and is distorted.

关 键 词: 电网 谐波 基波 有功电流 无功电流 三相电压不对称 无功补偿 电力系统 有源滤波器

领  域: [电气工程]

相关作者

相关机构对象

机构 华南师范大学

相关领域作者

作者 王珺
作者 刘洋
作者 张光宇
作者 叶飞
作者 周永务