帮助 本站公告
您现在所在的位置:网站首页 > 知识中心 > 文献详情
文献详细Journal detailed

电容器组中熔断器非短路开断的电气特性
Abnormal-Fusing Electrical Characteristics of Fuse Used in Shunt Capacitor Bank

作  者: ; ; ; ;

机构地区: 华南理工大学电力学院

出  处: 《华南理工大学学报(自然科学版)》 2009年第11期95-99,共5页

摘  要: 外熔断器是直接与电容器串联的保护器件,实际运行中,熔断器自身的非短路开断是电容器组附件中故障率最高的.目前广泛应用于电力系统的并联电容器组普遍采用分体框架式结构,由多台电容器联接成双星形后再接入电力系统.文中分析了开断过程的电气特性,推导了开断时的等效电气模型,得到了故障过程中电容器组的各支路电压及电流的相位规律,利用并联电容器组实时监测装置的故障记录数据验证了分析的正确性,并提出了降低熔断器引起电容器组故障率的建议. Fuse is a protection device which directly connects with a capacitor in series. In practice, the abnormal fusing of fuse is of the highest fault ratio among the accessories of capacitor bank. Shunt capacitor bank is the compensation equipment generally used in power systems. It, commonly with framed structure, consists of several capacitors in a double-star structure linking to the power system. This paper analyzes the abnormal-fusing electrical characteristics of fuse, deduces an equivalent electrical model describing the fusing, and presents the phase rules of the voltage and the current of each branch in the capacitor bank with fault. The correctness of the investigation is then proved by the real-time fault data recorded by a monitoring equipment of shunt capacitor bank. Some suggestions for reducing the fault ratio of the capacitor bank are proposed in the end.

关 键 词: 并联电容器组 熔断器 等效电气模型 相位规律 故障记录

领  域: [电气工程]

相关作者

作者 孙卉

相关机构对象

机构 广东水利电力职业技术学院

相关领域作者

作者 王珺
作者 刘洋
作者 张光宇
作者 叶飞
作者 周永务